PID Controllers

4010 PID CONTROLLER

SENSOR INPUT Thermocouple (J,K,PT-PT-RH) RTD, PT-100 (OPTIONAL)
DISPLAY Dual Display (For Set Point & Current Temperature)
.56″ Height; Red/Green L.E.D.
41/2digit upto full range
ACCURACY 1% of Full Scale or ± 2°C. (Software Linerlized)
POWER SUPPLY 180 – 240 V AC (50/60 Hz)
CONTROL ACTION By PID Parameters, Setable in Auto Tuning Mode/Manual Mode. (optional)
CONTROL OUTPUT AVAILABLE Relay Control : AC 250V, 10Amp (Resistive Load) IC (NO/NC) Contact SSR Driving: 0/12V DC (Control Voltage Pulse Load Resistance more than 1000 ohms) (optional)
Current : 4-20mA DC (Load Resistance less than 800 ohms)
NO. OF OUTPUT STAGE 1 Stage
TEMPERATURE SETTING By Front Key Pad.
AMBIENT TEMP./HUMIDITY 0-50°C, 35 to 85% RH
REOLUTION 0.1°C up to 1600°C
HYSTERESIS Adjustable + 9.9°C TO -9.9°C,
SENSOR ERROR Adjustable + 9.9°C TO -9.9°C,
SCALING Auto Scaling after 1000°C,
DIMENSIONS 96(W) x 96(H) x 140mm(D)
SENSOR BREAK PROTECTION Auto Switch OFF on Sensor break, ‘OPEN‘ will be displayed.
BODY TYPE ABS
  • Lock facility available on Request.
  • SMPS input power supply available on request.